Skip to main content
Siemens 5SL4210-6CC — 2-Pole MCB (DIN Rail)

Siemens 5SL4210-6CC SENTRON MCB, 2P B 10A 10kA

MPN5SL4210-6CC
Active

Siemens SENTRON 5SL4 series, miniature circuit breaker, 5SL4210-6CC, 2-pole, B-curve, 10 A rated, 10 kA breaking capacity per EN 60898, 400 V AC, 2 width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4210-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL4210-6CC — Electrical
ParameterValue
Number of poles2
5SL4210-6CC — Protection
ParameterValue
Tripping characteristic classB
Overvoltage category3
5SL4210-6CC — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Protection degree (IP)IP20, with connected conductors

Product details

The 5SL4210-6CC: The B-curve (tripping characteristic class B) means the MCB trips at 3–5× rated current — designed for resistive and general-purpose loads in residential and infrastructure panels, not for high-inrush motor circuits. Rated 10 A continuous, so it protects a branch circuit sized for that load. Two-pole (2P) switching with no neutral pole switching — the neutral is not broken, so this is for single-phase or two-phase circuits where the neutral is common. Rated for 440 V AC maximum in multi-phase operation, which gives headroom above the 400 V nominal.

Accepts solid or stranded conductors from 0.75 to 25 mm², with screw terminals torqued to 2.5–3 N·m. Sealable and touch-protected per IP20 with connected conductors. Ambient temperature range -25 to +55 °C operating, -40 to +75 °C storage.

Frequently asked questions

Where can I buy 5SL4210-6CC and how do I get a price?

The 5SL4210-6CC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is 5SL4210-6CC's listed depth?

The overall depth is 76 mm, with an installation depth of 70 mm.

What conductor sizes does 5SL4210-6CC accept?

It accepts solid or stranded conductors from 0.75 to 25 mm².

Will 5SL4210-6CC drop into a panel specified around 5SL3120-6MB without rewiring?

Both are 2-pole SENTRON MCBs on 2 width units (36 mm) with the same DIN-rail footprint, so mechanical fit is identical. The 5SL4210-6CC is a B-curve 10 A / 10 kA; the 5SL3120-6MB is a different rating — verify the branch circuit's required current and breaking capacity before swapping.

MPN
5SL4210-6CC