Siemens 5SL4210-8 — 2-Pole MCB (DIN Rail)

Siemens 5SL4210-8 SENTRON MCB, 2P D 10A 10kA, 400V

MPN5SL4210-8
Active

Siemens SENTRON 5SL4210-8, 2-pole miniature circuit breaker, D tripping characteristic, 10 A rated current, 10 kA breaking capacity at 400 V AC, 2 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4210-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL4210-8 — Electrical
ParameterValue
Number of poles2
5SL4210-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SL4210-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL4210-8 — Environmental
ParameterValue
Pollution degree2
5SL4210-8 — Specifications
ParameterValue
Energy Limitation Class3

Product details

The Siemens 5SL4210-8 is a 2-pole SENTRON miniature circuit breaker with a D tripping characteristic, rated at 10 A and 10 kA breaking capacity per EN 60898 and IEC 60947-2 at 400 V AC. The D-curve is built for loads with high inrush — motor starters, small transformers, or capacitor banks — where the magnetic trip holds off until roughly 10–20× rated current, avoiding nuisance trips on startup.

Ratings and thermal derating

At 30 °C ambient the breaker carries the full 10 A; at 40 °C it derates to 9.24 A, at 45 °C to 8.8 A, and at 55 °C to 7.96 A. The DC-side rating is 72 V maximum, so this is an AC-primary breaker; for a DC sub-circuit at higher voltage you need a different pole configuration. IP20 with connected conductors — finger-safe once installed, but not protected against dripping water.

Sealable — you can lock the toggle position to prevent unauthorised switching.

Frequently asked questions

Where can I buy 5SL4210-8 and how do I get a price?

We source the 5SL4210-8 to order against an RFQ. Submit a request and we will confirm current availability and pricing at quote time.

What is the D-curve for on this breaker?

The D tripping characteristic is designed for loads with high inrush current — motor starters, small transformers, or capacitor banks — where the magnetic trip holds off until roughly 10–20× rated current to avoid nuisance trips on startup.

What is the breaking capacity of 5SL4210-8?

The breaking capacity is 10 kA per both EN 60898 and IEC 60947-2 at 400 V AC.