Siemens 5SL4213-6 — 2-Pole MCB (DIN Rail)

Siemens 5SL4213-6 SENTRON MCB, 2P B 13A 10kA 400V

MPN5SL4213-6
Active

Siemens SENTRON 5SL4213-6, miniature circuit breaker, 2-pole, B characteristic, 13 A rated current, 10 kA breaking capacity at 400 V AC, 2 MW units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4213-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL4213-6 — Electrical
ParameterValue
Number of poles2
Supply voltage at AC rated value400 V
5SL4213-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SL4213-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL4213-6 — Environmental
ParameterValue
Pollution degree2
At 30 °C rated value13 A
5SL4213-6 — Specifications
ParameterValue
At AC rated value13 A
According to EN 60898 rated value10 kA
Energy Limitation Class3

Product details

The Siemens 5SL4213-6 is a SENTRON miniature circuit breaker (MCB) — a 2-pole, B-curve device rated 13 A at 30 °C, with a 10 kA breaking capacity per both EN 60898 and IEC 60947-2 at 400 V AC.

Rated 13 A at 30 °C, but the thermal derating curve is published: 12.01 A at 40 °C, 11.44 A at 45 °C, 10.35 A at 55 °C. If your panel ambient runs at 40 °C, you're effectively working with a 12 A breaker — size up if the continuous load is right at 13 A. The 2-pole design (2 MW units, 36 mm wide) fits standard DIN-rail enclosures; depth is 76 mm (70 mm installation depth), so verify the enclosure depth if you're retrofitting into a shallow gland plate. Mounting position is any, which helps in tight layouts. IP20 with connected conductors — fine inside a panel, not for wet locations. Power loss per pole at rated current in hot state is 2.1 W; total 4.2 W for the 2-pole unit, a figure to factor into enclosure thermal calculations if you're packing multiple breakers in a small box.

Where it sits in the panel

Snap-on DIN-rail mount, 2 MW units wide (36 mm). The 50/60 Hz rating covers both mains frequencies globally.

Frequently asked questions

What is the breaking capacity of 5SL4213-6?

10 kA at 400 V AC per both EN 60898 and IEC 60947-2.

Where can I buy 5SL4213-6?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Siemens provide for 5SL4213-6?

The SENTRON series carries CE marking for the European market and is designed to EN 60898 and IEC 60947-2. RoHS and REACH compliance is standard for current-production Siemens MCBs; specific declarations are available on request.