Skip to main content
Siemens 5SL4216-0RC — 2-Pole MCB (DIN Rail)

Siemens Betagard 5SL4216-0RC MCB, 2-pole 16A Z-curve, 10kA

MPN5SL4216-0RC

Siemens Betagard miniature circuit breaker, 5SL4216-0RC, 2-pole, 16 A rated, Z tripping characteristic, 10 kA breaking capacity per EN 60898, 440 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4216-0RC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameBetagard
5SL4216-0RC — Electrical
ParameterValue
Number of poles2
5SL4216-0RC — Protection
ParameterValue
Tripping characteristic classZ
Overvoltage categoryIII
5SL4216-0RC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL4216-0RC — Environmental
ParameterValue
Pollution degree3

Product details

The Z curve is designed for semiconductor and sensitive electronic loads where the inrush is minimal but short-circuit protection must be fast — it trips between 2.5 and 5 times rated current, so it clears faults before silicon devices see damaging let-through energy. Breaking capacity is 10 kA per both EN 60898 and IEC 60947-2, which means it safely interrupts faults up to that level on a 415 V AC supply (440 V AC max multi-phase).

Rated 16 A at 50 °C ambient, but the continuous current is temperature-dependent: 17.4 A at 30 °C, 16.7 A at 40 °C, 15.6 A at 55 °C, and 15.2 A at 60 °C. If the panel ambient runs warm, size the upstream conductor and load accordingly — the 16 A nameplate is only valid at 50 °C. Mounting position is unrestricted, and the enclosure is sealable for tamper-evident applications.

Halogen-free and silicon-free construction, with touch protection on the terminals. The product designation per EN 61346-2 and IEC 81346-2 is F (protective device). No neutral conductor switching — this is a 2-pole breaker for line and switched phase only.

Frequently asked questions

How do I get current pricing and availability for the 5SL4216-0RC?

The 5SL4216-0RC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is the 5SL4216-0RC's depth and width?

The overall depth is 76 mm, installation depth is 70 mm, and the width is 36 mm (2 modular width units).

Will the 5SL4216-0RC drop into a panel specified around the 5SL3116-6MB without rewiring?

Both are 2-pole MCBs on a 36 mm DIN-rail footprint, so the mechanical fit is the same. The critical difference is the tripping characteristic: the 5SL4216-0RC uses a Z curve (2.5–5× In) for semiconductor protection, while the 5SL3116-6MB uses a B curve (3–5× In) for general-purpose loads. If the panel was wired for a B-curve device, the Z-curve will trip faster on inrush — verify the load type before swapping.

What compliance documentation does Siemens provide for the 5SL4216-0RC?

The breaker is halogen-free and silicon-free, rated for pollution degree 3 and overvoltage category III, with a 10 kA breaking capacity certified per EN 60898 and IEC 60947-2. Standard Siemens declarations of conformity (CE, UKCA) and material compliance (RoHS, REACH) are available on request.

MPN