Skip to main content
Siemens 5SL4250-7CC — 2-Pole MCB (DIN Rail)

Siemens 5SL4250-7CC SENTRON MCB, 2P C 50A 10kA

MPN5SL4250-7CC
Active

Siemens SENTRON 5SL4250-7CC, miniature circuit breaker, 2-pole, C-curve, 50 A, 10 kA breaking capacity per EN 60898 at 400 V AC, 2 MW DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL4250-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL4250-7CC — Electrical
ParameterValue
Number of poles2
Supply voltage at AC rated value400 V
5SL4250-7CC — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL4250-7CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL4250-7CC — Environmental
ParameterValue
Pollution degree2
5SL4250-7CC — Specifications
ParameterValue
According to EN 60898 rated value10 kA
Energy Limitation Class3

Product details

Siemens SENTRON 5SL4250-7CC — 50 A, 2-pole C-curve MCB

The Siemens SENTRON 5SL4250-7CC is a 2-pole miniature circuit breaker rated 50 A with a C tripping characteristic and a 10 kA breaking capacity at 400 V AC per EN 60898.

Rated operating voltage is 400 V AC for multi-phase operation, with a maximum of 440 V AC. Supply frequency is 50/60 Hz. The DC rating tops out at 72 V — usable for DC branch protection only at low voltage. The MCB is sealable, halogen-free, and silicon-free, which simplifies compliance for installations requiring low-corrosion or clean-room materials.

Panel integration and mechanical fit

Depth is 76 mm, height 90 mm, width 36 mm (2 MW). Mounting position is unrestricted — installs vertically, horizontally, or flat. IP20 with connected conductors, so the busbar area must be within a closed enclosure.

Frequently asked questions

Where can I buy 5SL4250-7CC and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Current pricing and lead time are confirmed at quote time — no stock count or shipping promise is stated here.

Will 5SL4250-7CC drop into a panel specified for 5SL6220-7?

Yes — both share the same 76 mm depth, 36 mm width (2 MW), 90 mm height, DIN-rail mounting, and SENTRON platform. The 5SL4250-7CC has a higher breaking capacity (10 kA vs 6 kA) and higher current rating (50 A vs 20 A); the panel busbar and cable sizing must support the higher load.

What compliance documentation does Siemens provide for 5SL4250-7CC?

The part carries EN 60898 certification for the 10 kA rating. It is halogen-free and silicon-free, which supports RoHS and low-emission material compliance. Full declarations (CE, UKCA, EAC) are typically available from the manufacturer's documentation portal.

MPN
5SL4250-7CC