Skip to main content
Siemens 5SL4301-6 — 3-Pole MCB (DIN Rail)

Siemens SENTRON 5SL4301-6 MCB, B-Curve 3P 1A 10kA

MPN5SL4301-6
Active

Siemens SENTRON 5SL4301-6, miniature circuit breaker, B-curve, 3-pole, 1 A at 400 V AC, 10 kA breaking capacity per EN 60898 and IEC 60947-2, IP20, 3 MW units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4301-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4301-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-210 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL4301-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2 W
5SL4301-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL4301-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL4301-6 is a B-curve miniature circuit breaker rated 1 A at 400 V AC, 3-pole construction, with a 10 kA breaking capacity certified to both EN 60898 and IEC 60947-2.

Thermal derating and ambient conditions

At 30 °C ambient the breaker holds its full 1 A rating; at 40 °C it derates to 0.96 A, at 45 °C to 0.94 A, and at 55 °C to 0.9 A. If this breaker sits near a heat source — say, adjacent to a drive or in a roof-mounted enclosure — account for the derating curve when sizing the circuit.

Depth is 76 mm (70 mm behind the panel). Width 54 mm (3 MW). Sealable terminals, halogen-free and silicon-free construction. IP20 with connected conductors. The 50/60 Hz rating covers global mains frequencies.

Frequently asked questions

What is the breaking capacity of the 5SL4301-6?

10 kA per both EN 60898 and IEC 60947-2 at 400 V AC. This is the standard interrupting rating for domestic and light commercial final circuits in Europe.

Where can I buy the 5SL4301-6?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the thermal derating for the 5SL4301-6 at elevated ambient temperatures?

At 40 °C derates to 0.96 A, at 45 °C to 0.94 A, and at 55 °C to 0.9 A. The full 1 A rating holds at 30 °C. The operating ambient range is -40 °C to 75 °C.

MPN