Skip to main content
Siemens 5SL4306-7CC — 3-Pole MCB (DIN Rail)

Siemens 5SL4306-7CC SENTRON MCB, 3P C-curve 6A, 10kA

MPN5SL4306-7CC
Active

Siemens SENTRON 5SL4306-7CC miniature circuit breaker, 3-pole, C-curve, 6 A rated, 10 kA breaking capacity at 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4306-7CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4306-7CC — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL4306-7CC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)0.7 W
5SL4306-7CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL4306-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)50 m/s² at 25 to 150 Hz

Product details

The Siemens 5SL4306-7CC is a SENTRON miniature circuit breaker (MCB) — 3-pole, C-curve tripping characteristic, rated 6 A at 400 V AC with a 10 kA breaking capacity per EN 60898. Rated current derates with ambient temperature: 5.76 A at 40 °C, 5.63 A at 45 °C, 5.5 A at 50 °C, 5.37 A at 55 °C. If your panel runs warm, size the load accordingly — the 6 A nameplate only holds at 30 °C. The 3-pole design handles three-phase circuits; the 400 V AC rated voltage and 440 V maximum multi-phase operation cover standard 230/400 V grids at 50/60 Hz.

Sealable, halogen-free, silicon-free construction for environments where outgassing matters. Vibration resistance rated at 50 m/s² over 25 to 150 Hz per IEC 60068-2-6, which covers typical industrial panel vibration. Power loss per pole is 0.7 W at rated current in hot operating state; total 2.1 W for the 3-pole unit — negligible for thermal budgeting inside a crowded enclosure.

Frequently asked questions

How do I get current pricing and availability for 5SL4306-7CC?

Pricing and availability are confirmed at quote time. Submit an RFQ against this order code; the part is sourced to order through independent distribution.

What is the C-curve tripping characteristic and what loads is it suited for?

The C-curve trips at 5 to 10 times the rated current (In), making it the standard choice for general-purpose branch circuits feeding resistive and light inductive loads such as contactors, relays, and small motor starters in residential and light commercial infrastructure.

What are the derated current values at elevated ambient temperatures?

At 30 °C the rated current is 6 A. It derates to 5.76 A at 40 °C, 5.63 A at 45 °C, 5.5 A at 50 °C, and 5.37 A at 55 °C. Size the load for your actual panel ambient temperature.

What is the breaking capacity and at what voltage?

The breaking capacity is 10 kA at 400 V AC per EN 60898. The maximum operating voltage for multi-phase operation is 440 V AC.

What compliance documentation is available for 5SL4306-7CC?

The part is a Siemens SENTRON MCB carrying CE marking per the Low Voltage Directive. It is rated for overvoltage category III and pollution degree 2. Specific RoHS/REACH declarations are available from Siemens on request.

MPN
5SL4306-7CC