Skip to main content
Siemens 5SL4306-7RC — Miniature Circuit Breakers (MCB)

Siemens 5SL4306-7RC SENTRON MCB, 3P C 6A 10kA 415V

MPN5SL4306-7RC
Active

Siemens SENTRON 5SL4306-7RC, miniature circuit breaker, 3-pole, C-curve, 6 A, 10 kA at 415 V AC, 1 MW width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL4306-7RC — Ratings
ParameterValue
Overvoltage categoryIII
5SL4306-7RC — Mechanical
ParameterValue
Width18 mm
Height90 mm
Depth76 mm

Product details

What it is and what it does

The Siemens SENTRON 5SL4306-7RC is a 3-pole miniature circuit breaker rated 6 A with a C tripping characteristic and a 10 kA breaking capacity per EN 60898 at 415 V AC. That 10 kA figure is the maximum prospective fault current it can safely interrupt — enough for most residential and light commercial distribution boards where the upstream transformer impedance keeps the short-circuit level below that threshold. The C-curve (magnetic trip between 5 and 10 times In) means it tolerates moderate inrush without nuisance tripping, so it suits mixed loads with some motor or capacitive start-up current. It occupies a single modular width unit (18 mm) on standard DIN rail, with a depth of 76 mm and an installation depth of 70 mm. The IP20 rating (with connected conductors) is typical for enclosed distribution boards — no special sealing needed inside the panel.

Integration notes

Mounts in any position on a standard DIN rail. The sealable design allows the installer to lock the toggle position after commissioning — useful for tamper-proofing in shared-access panels. Halogen-free and silicon-free construction reduces corrosive off-gassing risk in enclosed spaces. Supplementary devices (auxiliary switches, shunt trips, undervoltage releases) can be added on the right side via the product extension feature.

Environmental range

Rated for ambient temperatures from -40 °C to +75 °C, which covers unheated enclosures in cold climates and hot switchrooms. The power loss per pole at rated current in hot state is 0.86 W — negligible for thermal budgeting in a populated board. Mechanical service life is 10 000 operating cycles typical.

Frequently asked questions

What is the breaking capacity of 5SL4306-7RC?

The breaking capacity is 10 kA according to EN 60898 at 415 V AC. That rating is the maximum fault current it can safely interrupt under standard test conditions.

Will 5SL4306-7RC drop into a panel specified around 5SL4363-7?

No — the 5SL4363-7 is a 3-pole breaker with a 54 mm width (3 MW), while the 5SL4306-7RC is 18 mm wide (1 MW). The footprint is different; the panel would need a different DIN-rail layout.

Where can I buy 5SL4306-7RC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SL4306-7RC