Skip to main content
Siemens 5SL4308-8 — 3-Pole MCB (DIN Rail)

Siemens 5SL4308-8 SENTRON MCB, 3P, 8A, D Curve, 10kA

MPN5SL4308-8
Active

Siemens SENTRON 5SL4 miniature circuit breaker, 3-pole, 8 A rated current, D tripping characteristic, 10 kA breaking capacity, 400 V AC, 3 width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4308-8 — Identification
ParameterValue
Design / model code5SL4
Brand nameSENTRON
Number of poles3
Suitability for operationResidential buildings/infrastructure
5SL4308-8 — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-210 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SL4308-8 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Rated frequency50 Hz
5SL4308-8 — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SL4308-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperature+55 °C, max. 95% humidity

Product details

The Siemens 5SL4308-8 is a 3-pole miniature circuit breaker from the SENTRON 5SL4 series, rated at 8 A with a D tripping characteristic. It breaks fault currents up to 10 kA per EN 60898 and IEC 60947-2, which means it can safely interrupt high-energy short circuits in residential and infrastructure distribution boards without cascading upstream.

D-curve tripping means the breaker holds through inrush currents up to 10–14× rated current — sized for motor-starting loads on pumps, compressors, or conveyor drives where a B- or C-curve would nuisance-trip on the inductive kick. At 8 A rated current, it protects a 3-phase motor circuit drawing roughly 4 kW on a 400 V supply. Three width units at 54 mm wide snap onto standard DIN rail. Depth of 76 mm and installation depth of 70 mm mean it fits flush in a 100 mm deep enclosure with room for gland plates and wiring. Terminal capacity accepts solid or stranded conductors from 0.75 to 25 mm², covering most branch-circuit wiring sizes.

Frequently asked questions

Where can I buy 5SL4308-8 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is the depth of 5SL4308-8?

Depth is 76 mm; installation depth behind the panel is 70 mm.

What wire sizes does 5SL4308-8 accept?

Terminals accept solid and stranded conductors from 0.75 to 25 mm².

Will 5SL4308-8 drop into a panel specified around 5SL4363-7 without rewiring?

Both are 3-pole SENTRON 5SL4 breakers on the same DIN-rail footprint and terminal range, so mechanical fit is identical. The difference is the tripping curve: 5SL4308-8 is D-curve (8 A), while 5SL4363-7 is a different rating — verify the load's inrush profile before swapping.

MPN