Skip to main content
Siemens 5SL4310-6 — 3-Pole MCB (DIN Rail)

Siemens 5SL4310-6 SENTRON MCB, 3P B 10A 10kA

MPN5SL4310-6
Active

Siemens SENTRON 5SL4310-6 miniature circuit breaker, 3-pole, B-curve, 10 A, 10 kA breaking capacity per EN 60898 and IEC 60947-2, 400 V AC, 3 MW units wide.

$65.67 – $71.37Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SL4310-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4310-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-210 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL4310-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.9 W
Mechanical service life (operating cycles, typ.)10 000
5SL4310-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL4310-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

What it is and what the ratings mean

The Siemens 5SL4310-6 is a SENTRON miniature circuit breaker (MCB) — a 3-pole, B-curve unit rated for 10 A at 400 V AC, with a 10 kA breaking capacity certified to both EN 60898 and IEC 60947-2. The B-curve trips between 3 and 5 times rated current, making it the standard choice for resistive and general-purpose loads in residential and light commercial distribution boards — not for motor-starting inrush, where a C or D curve would be specified. The 10 kA SCCR means it safely interrupts a fault up to that level without upstream coordination failure, which is the typical requirement for a sub-distribution board fed from a larger transformer.

Panel fit and integration

Occupies 3 modular width units (54 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm — standard for a 3-pole MCB in a SENTRON distribution board. IP20 with connected conductors, so it's intended for enclosed panel mounting, not washdown or outdoor exposure. Sealable design allows the installer to lock the toggle position after commissioning. Mounting position is any, which simplifies layout in tight enclosures.

Environmental and compliance

Halogen-free and silicon-free construction, rated for ambient temperatures from -40 °C to 75 °C, with a degree of pollution 2 and overvoltage category III — suitable for fixed installations in residential and infrastructure applications. Supplementary devices (auxiliary switches, shunt trips, alarm contacts) can be installed on the side, which is useful for remote status monitoring or emergency shutdown circuits.

Frequently asked questions

What is the difference between 5SL4310-6 and 5SL4363-7?

Both are 3-pole SENTRON MCBs with the same 10 kA breaking capacity and physical footprint (76 mm depth, 54 mm width). The difference is the trip curve: 5SL4310-6 is a B-curve (3–5× In, for resistive loads), while 5SL4363-7 is a C-curve (5–10× In, for moderate inductive loads like small motors or fluorescent lighting). They are mechanically interchangeable — same DIN-rail footprint, same terminal layout — but the trip coordination changes, so swap only if the load profile matches.

Where can I buy 5SL4310-6 and get current pricing?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What compliance documentation does Siemens provide for 5SL4310-6?

The MCB carries certifications to EN 60898 and IEC 60947-2 for breaking capacity. It is halogen-free and silicon-free, and rated for overvoltage category III and pollution degree 2. Standard RoHS/REACH declarations are available from the manufacturer.

MPN
5SL4310-6