Skip to main content
Siemens 5SL4310-7CC — 3-Pole MCB (DIN Rail)

Siemens 5SL4310-7CC SENTRON MCB, 3-pole C 10 A, 10 kA

MPN5SL4310-7CC
Active

Siemens SENTRON 5SL4310-7CC miniature circuit breaker, 3-pole, C-curve, 10 A rated at 400 V AC, 10 kA breaking capacity per EN 60898, IP20 with conductors, halogen-free, silicon-free, sealable.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4310-7CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4310-7CC — Protection
ParameterValue
Tripping characteristic (curve)C
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL4310-7CC — Electrical
ParameterValue
Rated current (AC)10 A
Rated voltage (AC, multi-phase)440 V
5SL4310-7CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL4310-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

It is a 3-pole unit with C-curve tripping characteristic, rated 10 A at 400 V AC, and a 10 kA breaking capacity per EN 60898.

The derating table is the real-world selector: at 30 °C ambient the breaker carries the full 10 A, but at 40 °C it derates to 9.24 A, at 45 °C to 8.83 A, at 50 °C to 8.41 A, and at 55 °C to 7.96 A. Rated for 50/60 Hz, overvoltage category III, pollution degree 2, and vibration tested to 50 m/s² at 25 to 150 Hz per IEC 60068-2-6. That vibration spec means it holds up on a machine-mounted subpanel near a compressor or conveyor drive.

Sealable with a lead or tag, halogen-free and silicon-free, so it meets clean-environment requirements for food processing or semiconductor fab subpanels.

Frequently asked questions

What is the breaking capacity of the 5SL4310-7CC?

10 kA per EN 60898 at 400 V AC, 3-pole operation.

What is the derated current at elevated ambient temperatures?

At 40 °C the rated current is 9.24 A, at 45 °C it is 8.83 A, at 50 °C it is 8.41 A, and at 55 °C it is 7.96 A.

Where can I buy the 5SL4310-7CC?

Sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does Siemens provide for the 5SL4310-7CC?

The MCB carries EN 60898 listing, is halogen-free and silicon-free, and is rated for overvoltage category III and pollution degree 2 per IEC standards.

MPN
5SL4310-7CC