Skip to main content
Siemens 5SL4310-8CC — 3-Pole MCB (DIN Rail)

Siemens 5SL4310-8CC SENTRON MCB, 3P D 10A 10kA 400V

MPN5SL4310-8CC
Active

Siemens SENTRON 5SL4310-8CC miniature circuit breaker, 3-pole, D tripping characteristic, 10 A rated current, 10 kA breaking capacity at 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4310-8CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4310-8CC — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree2
5SL4310-8CC — Electrical
ParameterValue
Rated current (AC)10 A
Rated voltage (AC, multi-phase)440 V
5SL4310-8CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL4310-8CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL4310-8CC is a SENTRON miniature circuit breaker (MCB) — a 3-pole unit with a D tripping characteristic, rated 10 A at 400 V AC and a 10 kA breaking capacity per EN 60898. Suitability for residential buildings and infrastructure is stated, but the 10 kA SCCR and overvoltage category III also make it a common choice in commercial distribution boards and light industrial sub-panels.

Ratings that matter for fit

The 10 A rating at 30 °C derates to 9.24 A at 40 °C, 8.83 A at 45 °C, 8.41 A at 50 °C, and 7.96 A at 55 °C — so if the breaker lives in a warm enclosure or next to other heat sources, the actual continuous current it can carry drops. The 3-pole design with no neutral switching means it breaks all three phases but leaves the neutral through. The 3-module-width footprint (54 mm wide) and 76 mm depth fit standard DIN-rail enclosures.

Frequently asked questions

What is the D-curve tripping characteristic for?

The D characteristic (10–20× In magnetic trip) is designed for loads with high inrush current — typically motors, transformers, welding equipment, and large banks of fluorescent or LED lighting. It avoids nuisance tripping on startup that a B or C curve would see.

What are the key ratings of 5SL4310-8CC?

3-pole, 10 A rated current at 30 °C, 10 kA breaking capacity per EN 60898 at 400 V AC, D tripping curve. Operating temperature range is -40 °C to 75 °C.

Where can I buy 5SL4310-8CC and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
5SL4310-8CC