At 1.6 A it protects a branch circuit drawing about 0.7 kVA at 400 V three-phase. Breaking capacity of 10 kA at 400 V AC (per EN 60898 and IEC 60947-2) covers most residential and light commercial service-entrance fault levels in European 400/230 V networks. The 3-pole design switches all three phases simultaneously, which matters for three-phase motor or distribution subfeeds. Rated for 50/60 Hz supply, maximum operating voltage 440 V AC multi-phase, and DC rated up to 72 V.
Snap-on DIN rail mount, any position. Sealable with a lead seal or lockable cover — useful for utility-metered or tamper-evident circuits.