Skip to main content
Siemens 5SL4325-0RC — 3-Pole MCB (DIN Rail)

Siemens Betagard 5SL4325-0RC MCB, 25 A, 3P, Char Z, 10 kA

MPN5SL4325-0RC

Siemens Betagard, miniature circuit breaker MCB, 3-pole, 25 A, tripping characteristic Z, 10 kA breaking capacity, 415 V AC, 3 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4325-0RC — Identification
ParameterValue
Brand nameBetagard
Number of poles3
Pole configuration3P
5SL4325-0RC — Protection
ParameterValue
Tripping characteristic (curve)Z
Breaking capacity per IEC 60947-210 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SL4325-0RC — Electrical
ParameterValue
Rated current (AC)25 A
Rated voltage (AC, multi-phase)440 V
5SL4325-0RC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL4325-0RC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens Betagard 5SL4325-0RC is a 3-pole miniature circuit breaker rated 25 A at 415 V AC, with a 10 kA breaking capacity certified to both IEC 60947-2 and EN 60898. The Z tripping characteristic is the key differentiator here — it triggers between 2 and 3 times rated current, much tighter than a B (3-5x) or C (5-10x) curve. That makes it the right choice for protecting semiconductor circuits, control transformers, or sensitive electronics where the inrush isn't high but you need fast clearing on a fault. The 25 A AC rating at 30 °C derates to 23.4 A at 60 °C, so if the panel runs hot, factor that in.

Fit and integration — 3 MW, IP20, DIN rail

Halogen-free and silicon-free construction. Vibration resistance rated at 50 m/s² over 25 to 150 Hz per IEC 60068-2-6. The part carries the usual Siemens Betagard compliance suite — RoHS, REACH, CE, and UL/CSA certifications are standard for this series; specific certification documents are available on request.

Frequently asked questions

Where can I buy the 5SL4325-0RC and get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the depth of the 5SL4325-0RC?

The 5SL4325-0RC has a depth of 76 mm, with an installation depth of 70 mm.

What is the width of the 5SL4325-0RC?

The 5SL4325-0RC is 54 mm wide, which is 3 modular width units on a standard DIN rail.

Will the 5SL4325-0RC drop into a panel specified around the 5SL3340-7CC without rewiring?

Physically, yes — both are 3-pole, 3 MW DIN-rail MCBs. But the 5SL3340-7CC uses a C characteristic and the 5SL4325-0RC uses a Z characteristic. The different trip curves mean the protection coordination changes; verify the downstream load's inrush and fault profile before swapping without a coordination study.

What compliance documentation does Siemens provide for the 5SL4325-0RC?

The Betagard series carries RoHS, REACH, CE, and UL/CSA certifications as standard. Specific declarations and certificates are available on request.

MPN
5SL4325-0RC