Specifications

5SL4325-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL4325-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-210 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL4325-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3 W
Mechanical service life (operating cycles, typ.)10 000
5SL4325-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL4325-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The 5SL4325-6: The B curve (tripping between 3 and 5 times rated current) is the standard choice for residential and light commercial lighting and socket-outlet circuits — it's not for motor starting or transformer inrush, where a C or D curve would be needed. The 10 kA breaking capacity is rated per both EN 60898 and IEC 60947-2, so it's accepted across domestic and industrial distribution boards alike. At 400 V AC three-phase, it covers most European panel voltages; the maximum operating voltage is 440 V AC.

Depth is 76 mm, installation depth 70 mm — it clears a standard 80 mm deep enclosure without gland-plate interference. Mounting position any, which helps when the panel layout is tight.

Frequently asked questions

What is the breaking capacity of the 5SL4325-6?

10 kA rated per both EN 60898 and IEC 60947-2 at 400 V AC.

Will the 5SL4325-6 drop into a panel specified for the 5SL4363-7?

Yes — same 3-pole footprint, same 54 mm width, same 76 mm depth, same DIN-rail mounting. The only difference is the trip curve: B on the 5SL4325-6 versus C on the 5SL4363-7. If the panel was designed for a C-curve breaker, swapping to a B-curve may cause nuisance tripping on loads with higher inrush.

Where can I buy the 5SL4325-6?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SL4325-6