Skip to main content
Siemens 5SL4350-7CC — 3-Pole MCB (DIN Rail)

Siemens 5SL4350-7CC SENTRON MCB, 3P C 50A 10kA 400V

MPN5SL4350-7CC
Active

Siemens SENTRON 5SL4350-7CC, miniature circuit breaker, 3-pole, C-curve, 50 A, 10 kA breaking capacity at 400 V AC, 50 Hz, IP20, halogen-free.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4350-7CC — Identification
ParameterValue
Design / model code5SL4CC
Brand nameSENTRON
Number of poles3
Suitability for operationResidential buildings/infrastructure
5SL4350-7CC — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SL4350-7CC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Rated frequency50 Hz
5SL4350-7CC — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.25 mm²
Terminal tightening torque, min.0.75 mm²
SealableYes
5SL4350-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperature+55 °C, max. 95% humidity

Product details

The Siemens SENTRON 5SL4350-7CC is a 3-pole miniature circuit breaker rated 50 A with a C tripping characteristic. The 10 kA breaking capacity at 400 V AC (per EN 60898) tells you this breaker can safely interrupt a fault current up to that level without upstream damage, which is the minimum for most residential and light commercial distribution boards. The 400 V AC rated voltage (440 V max multi-phase) covers three-phase supply up to 400/440 V line-to-line. The rated frequency is 50 Hz, matching standard European mains.

This breaker snaps onto a standard 35 mm DIN rail, occupying 3 width units (roughly 54 mm on the rail). The overall dimensions are 90 mm height, 54 mm width, and 76 mm depth, with an installation depth of 70 mm — so it fits in most standard enclosures without protruding. Wire terminals accept 0.75 mm² to 25 mm², solid or stranded, and the unit is sealable to prevent tampering after commissioning. The overvoltage category 3 means it is designed for fixed installation with transient overvoltages up to 4 kV, typical for distribution boards. The energy limiting class 3 indicates it limits the let-through energy effectively, reducing stress on downstream wiring.

The product is designed for residential buildings and infrastructure applications. The manufacturer provides compliance documentation including RoHS, REACH, and UL/IEC declarations as part of the standard product documentation package. The unit carries touch protection (finger-safe terminals) and is vibration resistant to 50 m/s² at 25 to 150 Hz per IEC 60068-2-6.

Frequently asked questions

Where can I buy 5SL4350-7CC and how is it quoted?

The 5SL4350-7CC is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume requirements.

What is the depth of 5SL4350-7CC?

The depth is 76 mm, with an installation depth of 70 mm. The overall dimensions are 90 mm height, 54 mm width (3 width units), and 76 mm depth.

Does 5SL4350-7CC drop into a panel specified for 5SL6606-7YA?

Both are 3-pole C-curve MCBs on 35 mm DIN rail, so the mechanical fit is the same. However, the 5SL4350-7CC is rated 50 A / 10 kA, while the 5SL6606-7YA has different ratings — check your BOM requirements before swapping.

What compliance documentation does Siemens provide for 5SL4350-7CC?

The product is rated per EN 60898 and carries standard RoHS, REACH, and UL/IEC declarations as part of the documentation package. It is halogen-free, silicon-free, and vibration resistant per IEC 60068-2-6.

MPN
5SL4350-7CC