4-pole C-curve MCB for 400 V distribution
Rated 4 A at 30 °C, but the 5SL4404-7 derates to 3.84 A at 40 °C and 3.58 A at 55 °C. If your panel ambient runs at 40 °C (common in a sealed enclosure), the breaker's effective rating drops 4% — factor that into the load calculation. The device is rated for ambient up to 75 °C and down to -40 °C, with 95% humidity at 55 °C.
Mounting position is unrestricted. IP20 with connected conductors — fine inside a distribution board but not for wet locations.