Mounting position is unrestricted — horizontal, vertical, or flat — which simplifies panel layout when gland plates or busbar runs constrain orientation. Screw terminals accept solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m. The housing is sealable, halogen-free, and silicon-free, so it's suitable for environments where off-gassing or contamination is a concern.
Siemens 5SL4404-8 SENTRON MCB, 4A D-curve, 10kA, 4P
Siemens SENTRON 5SL4404-8 miniature circuit breaker, 4 A rated current, D tripping characteristic, 10 kA breaking capacity (EN 60898 / IEC 60947-2), 4-pole, 400 V AC, 72 x 90 x 76 mm.
Specifications
| Parameter | Value |
|---|---|
| Type / order code | 5SL4 |
| Brand name | SENTRON |
| Application suitability | Residential buildings/infrastructure |
| Parameter | Value |
|---|---|
| Number of poles | 4 |
| Pole configuration | 4P |
| Rated current (In), AC | 4 A |
| Rated voltage, AC (multi-phase) | 440 V |
| Rated voltage, DC (max.) | 60 V |
| Voltage type | AC |
| Rated frequency | 50 Hz |
| Parameter | Value |
|---|---|
| Tripping characteristic (trip curve) | D |
| Rated breaking capacity (Icn), per EN 60898 | 10 kA |
| Rated breaking capacity, per IEC 60947-2 | 10 kA |
| Overvoltage category | 3 |
| Degree of protection (IP) | IP20, with connected conductors |
| Neutral conductor switching | No |
| Touch protection | Yes |
| Parameter | Value |
|---|---|
| Width in modular units | 4 |
| Width | 72 mm |
| Height | 90 mm |
| Depth | 76 mm |
| Installation depth | 70 mm |
| Mounting position | any |
| Sealable | Yes |
| Parameter | Value |
|---|---|
| Halogen-free | Yes |
| Silicone-free | Yes |
| Influence of ambient temperature (derating) | +55 °C, max. 95% humidity |
| Parameter | Value |
|---|---|
| Mechanical service life (switching cycles, typ.) | 10 000 |
Product details
Frequently asked questions
What is the breaking capacity of 5SL4404-8?
10 kA rated breaking capacity per both EN 60898 and IEC 60947-2, so it safely interrupts fault currents up to that level in a 400 V AC circuit.
Where can I buy 5SL4404-8?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What is the difference between 5SL4404-8 and 5SL3120-6MB?
The 5SL4404-8 is a 4-pole, 4 A, D-curve MCB; the 5SL3120-6MB is a different variant — pole count and rating differ. They are not drop-in substitutes without verifying the circuit requirements.