Skip to main content
Siemens 5SL4404-8 — 4-Pole MCB (DIN Rail)

Siemens 5SL4404-8 SENTRON MCB, 4A D-curve, 10kA, 4P

MPN5SL4404-8
Active

Siemens SENTRON 5SL4404-8 miniature circuit breaker, 4 A rated current, D tripping characteristic, 10 kA breaking capacity (EN 60898 / IEC 60947-2), 4-pole, 400 V AC, 72 x 90 x 76 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4404-8 — Identification
ParameterValue
Type / order code5SL4
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4404-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC4 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL4404-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-210 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SL4404-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL4404-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)+55 °C, max. 95% humidity
5SL4404-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Mounting position is unrestricted — horizontal, vertical, or flat — which simplifies panel layout when gland plates or busbar runs constrain orientation. Screw terminals accept solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m. The housing is sealable, halogen-free, and silicon-free, so it's suitable for environments where off-gassing or contamination is a concern.

Frequently asked questions

What is the breaking capacity of 5SL4404-8?

10 kA rated breaking capacity per both EN 60898 and IEC 60947-2, so it safely interrupts fault currents up to that level in a 400 V AC circuit.

Where can I buy 5SL4404-8?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between 5SL4404-8 and 5SL3120-6MB?

The 5SL4404-8 is a 4-pole, 4 A, D-curve MCB; the 5SL3120-6MB is a different variant — pole count and rating differ. They are not drop-in substitutes without verifying the circuit requirements.

MPN
5SL4404-8