Skip to main content
Siemens 5SL4405-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL4405-7 SENTRON MCB, 4P C 0.5A 10kA

MPN5SL4405-7
Active

Siemens SENTRON 5SL4405-7 miniature circuit breaker, 4-pole, C-curve, 0.5 A rated current, 10 kA breaking capacity per EN 60898, 400 V AC, 4 width units (72 mm), IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4405-7 — Identification
ParameterValue
Type / order code5SL4
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4405-7 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC0.5 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL4405-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-210 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SL4405-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL4405-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)+55 °C, max. 95% humidity
5SL4405-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens SENTRON 5SL4405-7 is a 4-pole miniature circuit breaker rated 0.5 A with a C tripping characteristic and a 10 kA breaking capacity per EN 60898 (also 10 kA per IEC 60947-2). It is designed for 400 V AC multi-phase operation, with a maximum of 440 V AC. Terminal capacity accepts solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m.

Frequently asked questions

Where can I buy the 5SL4405-7?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 5SL4405-7?

10 kA per EN 60898 and also 10 kA per IEC 60947-2, at 400 V AC. This is the standard interrupting rating for this class of MCB in residential and light commercial panels.

What wire sizes does the 5SL4405-7 accept?

Solid and stranded conductors from 0.75 to 25 mm². The screw terminals require a tightening torque of 2.5 to 3 N·m.

What is the physical size of the 5SL4405-7?

72 mm wide (4 width units), 90 mm high, 76 mm deep, with an installation depth of 70 mm. It mounts on a standard DIN rail in any position.

MPN