Skip to main content
Siemens 5SL4415-8 — 4-Pole MCB (DIN Rail)

Siemens 5SL4415-8 SENTRON MCB, 4P, D-curve, 1.6 A, 10 kA

MPN5SL4415-8
Active

Siemens SENTRON 5SL4 miniature circuit breaker, 4-pole, D tripping characteristic, 1.6 A rated current, 10 kA breaking capacity, 400 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SL4415-8 — Identification
ParameterValue
Type / order code5SL4
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure

Ratings

5SL4415-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC1.6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz

Protection

5SL4415-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-210 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes

Mechanical

5SL4415-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes

Environmental

5SL4415-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)+55 °C, max. 95% humidity

Performance

5SL4415-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

What this MCB does and where it fits

The Siemens 5SL4415-8 is a 4-pole miniature circuit breaker from the SENTRON 5SL4 series, rated at 1.6 A with a D tripping characteristic. That D-curve means it tolerates short-duration inrush currents up to 10–20× rated — designed for loads like small motors, transformers, or solenoid banks where the start-up surge would nuisance-trip a B or C curve. The 10 kA breaking capacity per EN 60898 and IEC 60947-2 tells you it can safely interrupt fault currents up to that level without welding contacts or cascading upstream. Rated 400 V AC for multi-phase operation, with a maximum of 440 V AC. This breaker snaps onto a standard DIN rail (72 mm wide, 4 width units) and mounts in any position. The IP20 rating with connected conductors is typical for enclosed distribution boards — it's not meant for wet or dusty environments. Ambient temperature range of -25 to +55 °C covers most indoor panel conditions. Terminal capacity accepts solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m.

Frequently asked questions

How do I get current pricing and availability for 5SL4415-8?

Submit an RFQ through this listing. We source the part through independent distribution and confirm pricing and stock at quote time.

What is the breaking capacity of 5SL4415-8?

10 kA per EN 60898 and IEC 60947-2, at 400 V AC.

What conductor sizes does the 5SL4415-8 terminal accept?

Solid or stranded conductors from 0.75 to 25 mm². Tightening torque is 2.5 to 3 N·m.

MPN
5SL4415-8