Siemens 5SL4432-7CC SENTRON MCB, 4P C 32A 10kA, 400V

MPN5SL4432-7CC
Active

Siemens SENTRON 5SL4432-7CC, 4-pole miniature circuit breaker, C-curve, 32 A rated, 10 kA breaking capacity per EN 60898 at 400 V AC, 4 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4432-7CC — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4432-7CC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC32 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)72 V
5SL4432-7CC — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL4432-7CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4432-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL4432-7CC is a SENTRON miniature circuit breaker (MCB) — a 4-pole, C-curve unit rated 32 A at 400 V AC, with a 10 kA breaking capacity per EN 60898.

Derating and mounting

At 40 °C it derates to 30.31 A, at 45 °C to 29.43 A, at 50 °C to 28.52 A, and at 55 °C to 27.58 A. The breaker mounts in any position (vertical, horizontal, upside down) and snaps onto standard DIN rail. It occupies 4 modular width units (about 72 mm of rail space). It's also sealable — you can lock the toggle in the off position with a padlock for LOTO compliance.

This breaker fits a standard DIN-rail enclosure and is rated for residential buildings and infrastructure (per the suitability listing). It carries IP20 protection with connected conductors — fine inside a closed panel, not for wet or outdoor use without an enclosure. If you're looking at the 5SL3340-7CC as a possible substitute, note the pole count: the 5SL3340-7CC is a 3-pole unit. The 5SL4432-7CC is 4-pole, so it handles three-phase-plus-neutral or a separate switched neutral. The width difference is one modular unit (3 MW vs 4 MW). No rewiring of the panel bus is needed if the original design allowed for the wider footprint, but the neutral pole wiring must be accounted for.

Sourcing and compliance

Compliance documentation — RoHS, REACH, and the IEC/EN standards listed on the nameplate — is available with the shipment.