That dual rating means the same part meets the SCCR requirement for most sub-distribution boards and final-load circuits without needing a separate upstream current-limiting device. Multi-phase operation is rated at 440 V AC maximum, giving headroom above the nominal 400 V for voltage swell conditions.
Mounting position is unrestricted, so the breaker can be installed horizontally or upside-down without derating the thermal-magnetic trip. IP20 with connected conductors — finger-safe from the front once wired, but not rated for washdown. Suitable for indoor panel use in residential buildings and infrastructure (schools, offices, light commercial).
Power loss and supplementary devices
Per-pole power loss at rated current in hot operating state is 3.3 W, so the total 4-pole dissipation is 13.2 W at full load.