It's a 1P+N pole configuration — switching the line and switching the neutral — with a C tripping characteristic, rated 6 A at 230 V AC. The 10 kA breaking capacity (acc. to EN 60898) means it can safely interrupt a fault current up to 10,000 A without welding its contacts or cascading damage upstream — that's the standard rating for most domestic and light commercial distribution boards across Europe.
At 6 A it protects a 1.38 kW resistive load at 230 V, or a motor starting current that briefly peaks under 60 A. The 1P+N configuration with neutral switching means the neutral pole opens and closes with the line pole, which is required in some national wiring rules for final circuits. The 2-module width (36 mm,) takes two 18 mm DIN-rail positions — standard for a 1P+N MCB in the 5SL family.
Vibration resistance 50 m/s² at 25 to 150 Hz per IEC 60068-2-6 — holds up on machinery near moderate vibration sources.