The Siemens 5SL4506-8 is a SENTRON miniature circuit breaker (MCB) rated 6 A with a D tripping characteristic, 1P+N poles, and a 10 kA breaking capacity per both EN 60898 and IEC 60947-2 at 230 V AC. It switches the neutral conductor as well, so it isolates both poles on a fault, which is standard for single-phase residential or light commercial sub-distribution.
Mounting position is any orientation. Sealable and touch-protected, which matters for installations requiring lockout/tagout compliance.
Thermal Derating & Environment
At 30 °C ambient the continuous rating is 6 A; at 40 °C it derates to 5.68 A, at 45 °C to 5.52 A, and at 55 °C to 5.17 A. If the panel runs warm, size the upstream protection accordingly. Halogen-free and silicon-free construction.