Skip to main content
Siemens 5SL4513-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL4513-7 SENTRON MCB, 1P+N, C-Curve, 13A, 10kA

MPN5SL4513-7
Active

Siemens SENTRON 5SL4513-7, miniature circuit breaker, 1P+N, C-curve, 13 A rated, 10 kA breaking capacity per EN 60898, 230 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4513-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityResidential buildings/infrastructure
5SL4513-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SL4513-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4513-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL4513-7 is a SENTRON miniature circuit breaker (MCB) in a 1P+N configuration, rated 13 A at 230 V AC with a C tripping characteristic and 10 kA breaking capacity per EN 60898 and IEC 60947-2. At 40 °C ambient the continuous rating derates to 12.01 A, and at 55 °C to 10.35 A; the unit is rated for ambient temperatures from -40 °C to +75 °C.

Panel fit and environmental constraints

Rated IP20 with connected conductors — suitable for enclosed distribution panels in residential and infrastructure builds.

Frequently asked questions

What are the key ratings of the 5SL4513-7?

Rated 13 A at 230 V AC, C-curve (trips at 5–10× In), 10 kA breaking capacity per EN 60898 and IEC 60947-2, 1P+N configuration with neutral switching. Ambient temperature range -40 °C to +75 °C, with derating above 30 °C.

Where can I buy the 5SL4513-7?

The 5SL4513-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation is available for the 5SL4513-7?

The MCB is designed to EN 60898 and IEC 60947-2, carries overvoltage category III and pollution degree 2, and the housing is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations should be requested at quote time as they are not included in the standard spec record.

Will the 5SL4513-7 drop into a panel specified for the 5SL6550-7BB?

Both are 2-MW (36 mm wide) SENTRON MCBs on the same DIN-rail footprint, so mechanical fit is identical. However, the 5SL6550-7BB is a different rating and pole configuration — verify the specific electrical ratings (current, voltage, breaking capacity, curve) against your BOM before substituting.

MPN
5SL4513-7