Skip to main content
Siemens 5SL4514-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL4514-7 SENTRON MCB, 2-pole 1P+N, C-curve, 0.3 A,

MPN5SL4514-7
Active

Siemens SENTRON 5SL4514-7 miniature circuit breaker, 1P+N, C-curve, 0.3 A rated, 230 V AC, 10 kA breaking capacity per EN 60898 / IEC 60947-2, 2 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4514-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityResidential buildings/infrastructure
5SL4514-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SL4514-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL4514-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Part identity and key ratings

The Siemens SENTRON 5SL4514-7 is a 1P+N miniature circuit breaker rated 0.3 A at 230 V AC, with a C tripping characteristic and a 10 kA breaking capacity per EN 60898 and IEC 60947-2.

At 0.3 A rated, it protects a very low-current branch circuit; the 10 kA breaking capacity (both EN 60898 and IEC 60947-2) ensures it can safely interrupt a fault up to that level without upstream damage. Rated current derates with ambient temperature: 0.3 A at 30 °C, 0.28 A at 40 °C, and 0.26 A at 55 °C.

Where it is used

This MCB is designed for residential buildings and infrastructure — final subcircuit protection in distribution boards where the load is low (lighting, small control transformers, alarm systems).

Frequently asked questions

What is the breaking capacity of 5SL4514-7?

10 kA per EN 60898 and IEC 60947-2 at 230 V AC.

What does the C-curve mean on this breaker?

The C-curve trips at 5–10 times rated current, making it suitable for moderate inrush loads such as lighting circuits and small transformers.

Where can I buy 5SL4514-7?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN