It is a 1P+N unit — switching the live pole and switching the neutral — rated 230 V AC (250 V AC in single-phase operation), with a 10 kA breaking capacity per both EN 60898 and IEC 60947-2.
20 A continuous rating and 10 kA SCCR at 230/250 V AC define the fault-clearing capability. Energy limiting class 3 means it restricts let-through energy during a fault — less stress on downstream wiring and connected equipment compared to class 1 or 2 breakers. The 1P+N configuration with neutral switching is common in single-phase final subcircuits where isolating both poles is required by local wiring rules; the neutral pole is not overcurrent-protected, only switched.
Screw terminals accept 0.75–25 mm² solid or stranded copper; tighten to 2.5–3 N·m. Mounting position any orientation; ambient range –25 to +55 °C, storage –40 to +75 °C. IP20 with conductors connected — suitable for enclosed distribution boards only, not for wet or dust-exposed locations.