The Siemens SENTRON 5SL4601-6 is a 4-pole miniature circuit breaker (3P+N) with B tripping characteristic, rated 1 A at 400 V AC. Breaking capacity is 10 kA under both EN 60898 and IEC 60947-2, so it handles fault currents up to that level without upstream cascade — a solid figure for residential or light commercial distribution boards where the prospective short-circuit current is known. Terminals accept solid or stranded conductors from 0.75 to 25 mm², tightened to 2.5–3 N·m. The 4 MW width (72 mm) snaps onto standard DIN rail; installation depth is 70 mm, overall depth 76 mm. Sealable, halogen-free, silicon-free — suited for environments where outgassing or tamper evidence matters.

Siemens 5SL4601-6 SENTRON MCB, 4P, B Curve, 1 A, 10 kA
MPN5SL4601-6
Active
Siemens SENTRON 5SL4601-6, 4-pole miniature circuit breaker, B characteristic, 1 A rated current, 10 kA breaking capacity, 400 V AC, 4 MW units.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Overvoltage category | 3 |
| Parameter | Value |
|---|---|
| Width | 72 mm |
| Height | 90 mm |
| Depth | 76 mm |
Product details
Frequently asked questions
What is 5SL4601-6's listed depth?
The overall depth is 76 mm; the installation depth (behind the panel face) is 70 mm.
What conductor sizes does 5SL4601-6 accept?
Solid conductors from 0.75 to 25 mm² and stranded conductors from 0.75 to 25 mm².
MPN
5SL4601-6