Skip to main content
Siemens 5SL4603-8 — 4-Pole MCB (DIN Rail)

Siemens 5SL4603-8 SENTRON MCB, 4P D-Curve 3A 10kA

MPN5SL4603-8
Active

Siemens SENTRON 5SL4603-8, 4-pole 3P+N miniature circuit breaker, D tripping curve, 3 A rated at 400 V AC, 10 kA breaking capacity, 4 MW units wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4603-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4603-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC3 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
5SL4603-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-210 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SL4603-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4603-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)+55 °C, max. 95% humidity

Product details

The Siemens 5SL4603-8 is a 4-pole (3P+N) SENTRON miniature circuit breaker with a D tripping characteristic, rated 3 A at 400 V AC and a 10 kA breaking capacity per EN 60898 and IEC 60947-2. That D-curve means it tolerates the high inrush of motor and transformer loads without nuisance tripping — the magnetic trip kicks in at 10–20× rated current, so it's the right choice for inductive circuits, not general lighting or resistive heaters. The 10 kA SCCR at 400 V tells you it can safely interrupt a fault up to that level without cascading upstream — coordination matters when you're protecting a distribution board feeding multiple motor starters.

Fit and integration

Snaps onto DIN rail; occupies 4 modular width units (72 mm wide). Depth is 76 mm, installation depth 70 mm — leaves clearance for wiring gutters in a standard 200 mm deep enclosure. Neutral conductor is switched (3P+N), so you get full isolation on all poles. Mounting position any, which helps when the panel layout is tight and you're rotating breakers to match busbar orientation. IP20 with connected conductors — fine inside a closed panel, not for wet environments.

Thermal derating and environment

Rated 3 A at 30 °C ambient; derates to 2.88 A at 40 °C and 2.69 A at 55 °C. If your panel runs hot — say a crowded MCC with drives below — the effective ampacity drops. The breaker is halogen-free and silicon-free, which matters for outgassing-sensitive environments like clean rooms or sealed enclosures near sensitive electronics. Temperature range -40 to 75 °C covers outdoor enclosures in cold climates. Sealable with a lockout provision for lockout/tagout compliance.

Frequently asked questions

What is the breaking capacity of the 5SL4603-8?

10 kA per both EN 60898 and IEC 60947-2 at 400 V AC. That's the maximum fault current it can safely interrupt.

What does the D tripping curve mean for this breaker?

D-curve means the magnetic trip operates at 10–20 times rated current (30–60 A for this 3 A unit). It's sized for motor and transformer inrush, not for resistive loads where a B or C curve would be a better fit.

Where can I buy the 5SL4603-8 and how is it quoted?

Sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, no stock figures on the public page.

MPN