Siemens 5SL4604-6 — 4-Pole MCB (DIN Rail)

Siemens 5SL4604-6 SENTRON MCB, 4A B-Curve 4-Pole 10kA

MPN5SL4604-6
Active

Siemens SENTRON 5SL4604-6 miniature circuit breaker, 400 V AC, 10 kA, 3P+N, B-curve, 4 A.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4604-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4604-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC4 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)72 V
5SL4604-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL4604-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4604-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL4604-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens 5SL4604-6 is a SENTRON miniature circuit breaker rated 400 V AC with a 10 kA breaking capacity per EN 60898 and IEC 60947-2. It's a 4-pole (3P+N) unit with a B-curve tripping characteristic, rated 4 A at 30 °C.

The 10 kA breaking capacity at 400 V AC means this MCB can safely interrupt a fault current up to 10,000 A without welding its contacts or cascading the fault upstream — that's the standard domestic and light-commercial SCCR for final subcircuits in most European and IEC-60364 installations. The B-curve (3–5× In) is the go-to for resistive and general-purpose loads; don't use it for motor starting unless the inrush is well under 20 A (4 A × 5 = 20 A peak). Temperature derating is baked in: at 40 °C ambient the continuous rating drops to 3.84 A, at 45 °C it's 3.76 A, and at 55 °C it's 3.58 A. The 72 mm width (4 modular units) is standard DIN-rail footprint for a 4-pole MCB — it snaps onto the rail and occupies four 18 mm spaces. Mounting position is any, so you can lay it sideways in a shallow enclosure if needed.

Energy limitation class 3 — fast enough to limit let-through energy for downstream equipment protection. Sealable terminals allow the installer to lock the cover after commissioning.

Frequently asked questions

What is the breaking capacity of the 5SL4604-6?

10 kA per both EN 60898 and IEC 60947-2 at 400 V AC. That's the standard interrupting rating for final subcircuits in residential and light-commercial panels.

What does the B-curve mean for this 4 A breaker?

The B-curve trips at 3 to 5 times rated current (12–20 A magnetic trip). It's suited for resistive loads, lighting, and general socket circuits. Not ideal for motor starting unless the inrush is under 20 A.

Where can I buy the 5SL4604-6?

Sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time.

Does the 5SL4604-6 have temperature derating?

Yes. At 40 °C the rating is 3.84 A, at 45 °C it's 3.76 A, and at 55 °C it's 3.58 A. Factor this into panel design if the ambient runs above 30 °C.