Skip to main content
Siemens 5SL4606-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL4606-7 SENTRON MCB, 400V 10kA, 3P+N, C-curve, 6A

MPN5SL4606-7
Active

Siemens SENTRON miniature circuit breaker, 5SL4606-7, 3P+N, C-curve, 6 A rated, 400 V AC, 10 kA breaking capacity per EN 60898 and IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4606-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4606-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SL4606-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL4606-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4606-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL4606-7 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.6 W

Product details

Where it goes and how it fits

The IP20 rating (with conductors connected) means it's meant for inside an enclosed panel, not out in the weather. It's sealable and halogen-free, silicon-free, so it's fine for clean-room or food-line environments where outgassing matters.

What the C-curve and 10 kA mean for your panel

The C-curve trips between 5 and 10 times rated current — so for a 6 A breaker, that's 30 to 60 A magnetic trip. That's enough headroom to start a small motor or a bank of fluorescent ballasts without nuisance tripping, but still fast enough to clear a hard short.

Temperature range and pollution degree

Pollution degree 2 means it's suited for normal indoor environments where only non-conductive dust accumulates — no condensation or conductive grime expected.

Frequently asked questions

Where can I buy 5SL4606-7 and get a price?

The 5SL4606-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 5SL4606-7 drop into a panel specified for 5SL4363-7?

The 5SL4606-7 is 4 modular width units (72 mm) wide, while the 5SL4363-7 is 3 modular width units (54 mm) wide. The 5SL4606-7 also includes a switched neutral pole (3P+N) that the 5SL4363-7 lacks. So it will not drop into the same DIN rail slot without freeing up an extra 18 mm of width, and the wiring for the neutral pole must be accounted for.

What is the depth of 5SL4606-7?

The depth is 76 mm, with an installation depth of 70 mm.

What compliance documentation is available for 5SL4606-7?

The 5SL4606-7 carries breaking capacity certifications per EN 60898 and IEC 60947-2, and is rated for overvoltage category III and pollution degree 2. It is halogen-free and silicon-free. For specific RoHS/REACH/UL declarations, the manufacturer's documentation is available on request.

MPN
5SL4606-7