Skip to main content
Siemens 5SL4610-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL4610-7 SENTRON MCB, 4P C-Curve 10A 10kA

MPN5SL4610-7
Active

Siemens SENTRON 5SL4610-7, miniature circuit breaker, 4-pole (3P+N), C-curve, 10 A rated, 400 V AC, 10 kA breaking capacity per EN 60898 and IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4610-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4610-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SL4610-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL4610-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4610-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL4610-7 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)0.9 W

Product details

The Siemens SENTRON 5SL4610-7 is a 4-pole miniature circuit breaker (3P+N) with a C-curve trip characteristic, rated at 10 A and 400 V AC. It provides a 10 kA breaking capacity under both EN 60898 and IEC 60947-2, which means it can safely interrupt fault currents up to that level in residential and infrastructure distribution boards. The 4-module-width (72 mm) body snaps onto standard DIN rail and accepts supplementary devices like shunt trips or auxiliary contacts.

What the ratings mean for fit

The 10 kA breaking capacity is the headline number for this class — it tells you the MCB can clear a bolted fault on a 400 V supply without welding its contacts or rupturing the case. That matches typical domestic and light commercial service-entrance requirements where the prospective short-circuit current stays under 10 kA. The C-curve trips between 5 and 10 times rated current, so it's sized for inductive loads like small motors, fluorescent lighting banks, or transformer inrush — not for pure resistive heaters (B-curve territory) or heavy motor starts (D-curve). The 4-pole 3P+N design switches all three phases and the neutral, with the neutral pole switching but not protecting — standard for TN or TT systems where you need a switched neutral for isolation. The 72 V DC maximum rating is a secondary capability for control circuits, not the primary application. Power loss per pole is 0.9 W at rated current in hot operating state. For a 4-pole breaker at full load that's 3.6 W total dissipated inside the enclosure — negligible in a ventilated board, but worth noting if you're packing multiple breakers into a sealed, thermally constrained panel.

Panel integration and compliance

Mounts on DIN rail in any position. The 72 mm width occupies 4 modular units. Installation depth behind the panel face is 70 mm, overall depth 76 mm. IP20 with connected conductors — protected against finger contact but not against moisture, so it belongs inside a distribution board, not in a washdown zone. Overvoltage category III and pollution degree 2 confirm it's rated for fixed-installation mains supply. Halogen-free and silicon-free construction — relevant for environments where outgassing from a fault could damage sensitive electronics or where silicone contamination must be avoided. Sealable for lockout/tagout compliance. Mechanical service life is 10,000 operating cycles typical.

Frequently asked questions

Will 5SL4610-7 drop into a panel specified around 5SL4363-7 without rewiring?

No. The 5SL4363-7 is a 3-pole (3P) breaker, 54 mm wide (3 modules). The 5SL4610-7 is 4-pole (3P+N), 72 mm wide (4 modules). It will not fit the same DIN-rail footprint without a wider mounting slot or a different enclosure cutout, and the wiring differs because the neutral pole is switched.

What compliance documentation does Siemens provide for 5SL4610-7?

The 5SL4610-7 carries ratings per EN 60898 and IEC 60947-2, with a 10 kA breaking capacity under both standards. It is rated for overvoltage category III and pollution degree 2. Standard Siemens documentation includes CE declaration of conformity and the product is halogen-free and silicon-free.

MPN
5SL4610-7