Skip to main content
Siemens 5SL4613-8CC — Miniature Circuit Breakers (MCB)

Siemens 5SL4613-8CC SENTRON MCB, 4P D 13A 10kA

MPN5SL4613-8CC
Active

Siemens SENTRON 5SL miniature circuit breaker, 4-pole (3P+N), D tripping characteristic, 13 A rated current, 10 kA breaking capacity per EN 60898, 400 V AC, 4 width units.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL4613-8CC — Ratings
ParameterValue
Overvoltage category3
5SL4613-8CC — Mechanical
ParameterValue
Width72 mm
Height90 mm
Depth76 mm

Product details

The Siemens SENTRON 5SL4613-8CC is a 4-pole (3P+N) miniature circuit breaker rated 13 A with a D tripping characteristic, breaking 10 kA per EN 60898 at 400 V AC.

Lifecycle status is active per the manufacturer record. The halogen-free and silicon-free construction simplifies compliance documentation for RoHS and REACH declarations — relevant if your quality system requires full material disclosure per IATF 16949 or similar.

Physical fit & mounting

Any mounting position is allowed. Conductor range 0.75 mm² to 25 mm², and the terminals are sealable — a feature for panel builders who need to lock out adjustments after commissioning. IP20 with connected conductors, so it belongs inside a closed enclosure, not exposed to washdown or dust.

Coordination note

The single-pole peer 5SL4120-7CC (20 A, C-curve) shares the same 76 mm depth and 90 mm height but is 18 mm wide — one width unit. It will not drop into a panel cutout or DIN-rail position sized for the 4-pole 5SL4613-8CC without adding three adjacent slots and rewiring the neutral leg (the single-pole version does not switch neutral). If your panel was laid out for the 5SL4120-7CC, the 5SL4613-8CC needs 72 mm of rail space, not 18 mm.

Rated for vibration per IEC 60068-2-6 at 50 m/s² over 25 to 150 Hz. Ambient temperature limit is +55 °C with up to 95% humidity. Overvoltage category III, touch protection fitted.

Frequently asked questions

What is the breaking capacity of 5SL4613-8CC?

10 kA per EN 60898 at 400 V AC. That rating is the short-circuit capacity the breaker can safely interrupt under standard test conditions.

Will 5SL4613-8CC fit in a panel designed for 5SL4120-7CC?

No. The 5SL4613-8CC is 72 mm wide (4 width units) and switches 3 phases plus neutral. The 5SL4120-7CC is 18 mm wide (1 width unit) and switches a single pole without neutral. The panel cutout and DIN-rail allocation are incompatible without rework.

Where can I buy 5SL4613-8CC?

Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

MPN
5SL4613-8CC