Skip to main content
Siemens 5SL5102-6CC — 1-Pole MCB (DIN Rail)

Siemens 5SL5102-6CC SENTRON MCB, 1P B2, 125 VDC, 10 kA

MPN5SL5102-6CC

Siemens SENTRON 5SL5102-6CC, 1-pole miniature circuit breaker, B-curve 2 A, DC rated 125 V at 10 kA breaking capacity, 1 MW unit, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL5102-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SL5102-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SL5102-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL5102-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

What this MCB is and where it fits

The Siemens SENTRON 5SL5102-6CC is a 1-pole miniature circuit breaker (MCB) with a B tripping curve, rated 2 A. It is designed for DC circuits up to 125 V with a breaking capacity of 10 kA — so it handles fault currents from battery banks, DC bus lines, or solar combiner boxes without cascading upstream. The B-curve (3-5 In) means it trips fast on moderate overloads, making it a fit for resistive or lightly inductive DC loads where inrush is low. It snaps onto a standard DIN rail and occupies 1 modular width unit (18 mm), so it fits tight panel layouts.

Physical fit and panel integration

The 5SL5102-6CC measures 18 mm wide, 90 mm high, and 76 mm deep — standard SENTRON 5SL form factor. Installation depth is 70 mm behind the panel face. Mounting position is any orientation. IP20 with connected conductors, so it lives inside a closed panel or distribution board. The housing is halogen-free and silicon-free, which matters for environments sensitive to outgassing (clean rooms, medical, food processing).

Key ratings and what they mean for your circuit

Rated DC voltage 72 V maximum per pole, but the description states 125 V DC — that is the voltage at which the 10 kA breaking capacity is certified. The B-curve characteristic (tripping between 3 and 5 times rated current) means a 2 A breaker will hold steady-state loads up to 2 A and trip between 6 A and 10 A. Overvoltage category III and pollution degree 2 confirm it is rated for fixed-installation distribution boards (not just final circuits). Touch protection is built in, and the unit is sealable for tamper-proof metering or rental applications.

Frequently asked questions

Where can I buy 5SL5102-6CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send your quantity and target delivery window.

Will 5SL5102-6CC drop into a panel specified around 5SL6132-6MB without rewiring?

Yes — both are 1-pole SENTRON 5SL-series MCBs with the same 18 mm width, 76 mm depth, and DIN-rail mounting. The 5SL6132-6MB is an AC-rated 32 A B-curve unit (6 kA at 400 V AC), while the 5SL5102-6CC is a DC-rated 2 A B-curve unit (10 kA at 125 V DC). The physical footprint is identical, so a swap requires no panel rework — just verify the circuit voltage and load current match the new breaker's rating.

What compliance documentation does Siemens provide for 5SL5102-6CC?

The product carries RoHS and halogen-free compliance by design. Full declarations (CE, UKCA, EAC) are available through the Siemens Industry Online Support portal. The part is not UL-listed (it is IEC/EN 60898 rated), so verify local code acceptance for DC distribution.

MPN
5SL5102-6CC