Rated 6 kA breaking capacity per IEC/EN 60898-1 at 230 V AC, it clears a fault up to that level without welding the contacts — enough for most final subcircuits in a TN or TT system. The 60 V DC rating covers control-voltage applications like relay coils or solenoid valves on a 48 V or 60 V DC bus.
Snaps onto a standard 35 mm DIN rail and occupies 1 modular width unit (18 mm,). The 76 mm depth and 70 mm installation depth mean it sits flush in a distribution board with standard 80 mm deep enclosures — no need to oversize the box. Mounting position is unrestricted, so it can be installed horizontally in a shallow panel if needed.
Designed to IEC/EN 60898-1 and GB/T10963.1. Halogen-free and silicon-free construction reduces corrosive off-gassing in a fire — relevant for installations in data centers or clean rooms. The part is sealable for anti-tamper applications. Vibration resistance per IEC 60068-2-6 is verified, and the mechanical service life is rated at 4 000 operating cycles typical.