Skip to main content
Siemens 5SL6006-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SL6006-7KL SENTRON MCB, 1P+N, C6, 6kA, 1MW

MPN5SL6006-7KL
Active

Siemens SENTRON 5SL6006-7KL, miniature circuit breaker compact, 1P+N, C-curve 6 A, 6 kA per IEC/EN 60898-1, 230 V AC, 1 modular width (18 mm).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6006-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL6006-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL6006-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodDIN rail
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6006-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The neutral pole switches with the line, so you get full isolation on both conductors when the breaker trips or is manually opened.

Snaps onto DIN rail and takes up one modular width at 18 mm. Mounting position any, so it fits in tight enclosures or horizontal busbar layouts. IP20 with conductors connected — standard for panel interiors, not for wet locations.

Rated for 230 V AC, 60 V DC, 50/60 Hz. Insulation voltage 250 V AC. Sealable for tamper-proofing after commissioning. Vibration-resistant per IEC 60068-2-6. Mechanical life 10 000 operating cycles typical.

Frequently asked questions

What is the breaking capacity of 5SL6006-7KL?

6 kA per IEC/EN 60898-1, which covers standard residential and commercial branch circuits.

What is the width of 5SL6006-7KL?

18 mm, one modular unit — fits a standard DIN-rail slot.

Will 5SL6006-7KL drop into a panel specified around 5SL6120-7?

The 5SL6120-7 is a 20 A version in the same SENTRON 5SL6 family, same 1P+N form factor and 18 mm width — it shares the same DIN-rail footprint and terminal layout, so a swap is a straight pull-and-replace without rewiring, provided the ampacity matches the circuit requirements.

How do I get current pricing and availability for 5SL6006-7KL?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What compliance documentation does Siemens provide for 5SL6006-7KL?

The breaker is certified to IEC/EN 60898-1 and GB/T 10963.1. It is halogen-free and silicon-free. Specific RoHS/REACH declarations and UL listing status should be verified against the manufacturer's current documentation at time of order.

MPN
5SL6006-7KL