Skip to main content
Siemens 5SL6008-7 — Miniature Circuit Breakers (MCB)

Siemens 5SL6008-7 SENTRON MCB, 8A C-Curve, 6kA, 1-module

MPN5SL6008-7
Active

Siemens SENTRON 5SL6008-7 miniature circuit breaker, 8 A, C characteristic, 6 kA per EN 60898, 1-module width, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6008-7 — Ratings
ParameterValue
Overvoltage categoryIII
5SL6008-7 — Mechanical
ParameterValue
Width18 mm
Height90 mm
Depth76 mm

Product details

The Siemens 5SL6008-7 is a SENTRON miniature circuit breaker (MCB) rated 8 A at AC with a C tripping characteristic and a 6 kA breaking capacity per EN 60898. It occupies one modular unit (18 mm wide) on standard DIN rail, making it a direct fit for residential and infrastructure distribution boards where branch-circuit overcurrent protection is needed for general-purpose loads like lighting, socket outlets, and small appliances.

Ratings and derating

At 30 °C ambient the breaker carries its full 8 A rating. At 40 °C it derates to 7.52 A, at 50 °C to 7 A, and at 60 °C to 6.45 A. If the panel runs warm — near a transformer or in a crowded enclosure — the effective trip point shifts; size the upstream load against the derated figure at your expected ambient, not the 30 °C nameplate. The C characteristic means the magnetic trip fires at 5 to 10 times rated current — typical for circuits with moderate inrush from small motors or capacitive loads. The 6 kA breaking capacity at 250 V AC per EN 60898 covers most residential and light-commercial fault levels; verify the prospective short-circuit current at the installation point stays under that limit.

Mounting and integration

Snaps onto standard DIN rail (EN 60715) in any mounting position. Depth is 76 mm, width 18 mm, height 90 mm; the required installation depth behind the panel is 70 mm. One modular-width unit leaves adjacent slots free for other SENTRON devices. The top and bottom terminals are not combined — each pole terminates independently. Touch protection is built in, and the breaker is sealable for tamper-proofing after commissioning. Rated for overvoltage category III and pollution degree 2, which covers fixed-installation distribution boards. IP20 with connected conductors — suitable for enclosed panels, not for washdown or outdoor exposure.

Frequently asked questions

What is the 5SL6008-7 rated current and breaking capacity?

It is rated 8 A at AC with a C tripping characteristic and a 6 kA breaking capacity per EN 60898 at 250 V AC.

Will the 5SL6008-7 drop into a panel specified around the 5SY6006-7?

Both are 1-module (18 mm) DIN-rail MCBs from the same SENTRON family with similar dimensions, so mechanical fit is the same. The 5SL6008-7 is rated 8 A C-curve versus the 5SY6006-7's 6 A B-curve — verify the load current and trip characteristic match your circuit before substituting.

What compliance documentation does Siemens provide for the 5SL6008-7?

The breaker is halogen-free and silicon-free, rated for overvoltage category III and pollution degree 2 per IEC. Standard Siemens declaration of conformity covers EN 60898; RoHS and REACH compliance documentation is available on request.

Where can I buy the 5SL6008-7 and how is it quoted?

The 5SL6008-7 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
5SL6008-7