The 5SL6013-6: The B-curve (tripping characteristic class B) means the breaker trips at 3–5× rated current — standard for residential and light commercial lighting or socket-outlet circuits where inrush is low. Derating is specified: 12.37 A at 40 °C, 12.05 A at 45 °C, 11.72 A at 50 °C, 11.37 A at 55 °C, 11.02 A at 60 °C — so if the panel ambient runs hot, size up accordingly.
Mounts on standard DIN rail (fastening method: standard rail) in any position. Depth is 76 mm, installation depth 70 mm, height 90 mm, width 18 mm (1 modular width). Sealable, halogen-free, silicon-free. Touch protection is provided. The neutral conductor can be switched via a compatible product component.