The Siemens SENTRON 5SL6016-7 is a 1P+N miniature circuit breaker with C-curve tripping characteristic, rated 16 A at 230 V AC and 6 kA breaking capacity per IEC/EN 60898-1.
The C16 curve means the breaker trips at 5–10× rated current (80–160 A magnetic trip), suited for circuits with moderate inrush — lighting banks, small motor loads, or general socket outlets. The 1P+N configuration switches both phase and neutral, which is required in many national wiring regulations for final circuits. Rated insulation voltage (Ui) is 250 V AC, with operating voltage max 250 V AC single-phase. The neutral conductor is switched, so the breaker isolates both poles when off — useful for maintenance isolation in single-phase panels.
Panel integration