Skip to main content
Siemens 5SL6020-7KL — 1-Pole MCB (DIN Rail)

Siemens 5SL6020-7KL SENTRON MCB, 20 A C-Curve, 1P+N, 6 kA

MPN5SL6020-7KL
Active

Siemens SENTRON 5SL6020-7KL miniature circuit breaker, 20 A, C-curve, 1P+N, 6 kA per EN 60898, 230 V AC, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6020-7KL — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SL6020-7KL — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Overvoltage categoryIII
5SL6020-7KL — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topNo
Combined terminal, bottomNo
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.24 V
SealableYes
5SL6020-7KL — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL6020-7KL is a 1P+N miniature circuit breaker rated 20 A with a C tripping characteristic, breaking capacity 6 kA per EN 60898 at 230 V AC. It switches the neutral conductor and is sealable — common for utility-metered sub-distribution where tamper evidence matters.

C-curve selectivity and wire range

The 20 A rating in C-curve means the magnetic trip fires between 100 A and 200 A; below that, the thermal bimetal handles overloads. Terminals accept 0.75…16 mm² solid or stranded copper, tightening torque 2…2.5 N·m (17.7…22.1 lbf·in). That wire range covers most final subcircuit conductors up to 4 mm² comfortably, with headroom for paralleled feeds if needed.

Integration note

Ambient -25…+45 °C, storage -40…+75 °C. Halogen-free and silicon-free construction, which matters for sensitive environments (clean rooms, food processing panels) where outgassing could contaminate optics or contacts.

Frequently asked questions

What is the breaking capacity of 5SL6020-7KL?

6 kA rated per EN 60898 at 230 V AC.

How do I get current pricing and availability for 5SL6020-7KL?

Submit an RFQ — we source through independent distribution and confirm pricing and availability at quote time.

Will 5SL6020-7KL drop into a panel specified around 5SY6008-7 without rewiring?

Both are 1P+N, 18 mm wide, DIN-rail mount MCBs with similar terminal ranges, so physical fit is the same. The 5SY6008-7 is an 8 A B-curve; the 5SL6020-7KL is a 20 A C-curve — the difference is rating and characteristic, not footprint. Verify the circuit load before substitution.