Siemens 5SL6102-6CC SENTRON MCB, 1P B-curve 2A 6kA

MPN5SL6102-6CC
Active

Siemens SENTRON 5SL6CC series, miniature circuit breaker, 1-pole, B-curve, 2 A, 6 kA breaking capacity, 230/400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6102-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SL6102-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Overvoltage category3
5SL6102-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6102-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

Rated single-phase at 250 V and multi-phase at 440 V AC, with a max 72 V DC for DC circuits if needed. Mounts in any position, IP20 with conductors connected, so it lives inside a distribution board or panel.

Snaps onto DIN rail, 18 mm per pole, so it takes up one width unit. Sealable per the spec, halogen-free and silicon-free construction. Rated for pollution degree 2, overvoltage category III, vibration resistance of 50 m/s² at 25 to 150 Hz per IEC 60068-2-6.

Compared to the 5SL4106-7CC, the 5SL6102-6CC shares the same 1-pole, B-curve, 2 A, 6 kA footprint — 18 mm wide, same depth. The difference is in the accessory interface: the 5SL6CC accepts the newer 5ST3 series auxiliaries and shunt trips, while the 5SL4 series uses the older 5ST1 accessories. If your panel is already built around 5SL4 breakers and you have spare accessories, the 5SL6102-6CC will physically drop into the same DIN rail slot and wire the same way, but your spare aux contacts won't clip on without an adapter.

Frequently asked questions

What is the breaking capacity of 5SL6102-6CC?

6 kA per EN 60898 at 230/400 V AC. That's the standard breaking capacity for residential and light commercial distribution boards.

Where can I buy 5SL6102-6CC and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the difference between 5SL6102-6CC and 5SL4106-7CC?

Both are 1-pole B-curve 2 A 6 kA MCBs with the same physical footprint. The 5SL6CC uses the newer 5ST3 accessory system; the 5SL4 series uses 5ST1. The breaker itself drops into the same panel slot and wires the same way.

MPN
5SL6102-6CC