Siemens SENTRON 5SL6102-7CC, miniature circuit breaker, 1-pole, C-curve, 2 A, 6 kA breaking capacity per EN 60898, 1 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6102-7CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL6102-7CC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL6102-7CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6102-7CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL6102-7CC is a 1-pole miniature circuit breaker rated 2 A with a C tripping characteristic and a 6 kA breaking capacity per EN 60898.

The C-curve trips between 5× and 10× rated current (10 A to 20 A for this 2 A unit), which suits loads with moderate inrush — think small transformers, capacitor banks, or groups of LED drivers. The 1-pole design switches only the line conductor, so it is used in single-phase circuits or as a branch protector in a multi-pole assembly. Rated operating voltage is 400 V AC for multi-phase use and 250 V AC for single-phase, with a maximum of 440 V AC. The supply frequency is 50/60 Hz.

The unit is halogen-free and silicon-free, meeting material restrictions for clean-room or high-reliability installations where outgassing must be controlled.

The breaker carries a 6 kA breaking capacity according to EN 60898, the harmonized European standard for MCBs in household and similar installations. The product is designed for residential buildings and infrastructure. Vibration resistance is tested to IEC 60068-2-6 at 50 m/s² over 25 to 150 Hz.

Frequently asked questions

How do I get pricing and availability for 5SL6102-7CC?

The 5SL6102-7CC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate.

What are the physical dimensions of 5SL6102-7CC?

Width is 18 mm (1 modular unit), depth is 76 mm, height is 90 mm, and installation depth behind the panel is 70 mm.

Will 5SL6102-7CC fit in a panel designed for 5SL4363-7?

Yes, the 5SL6102-7CC is 18 mm wide (1 MW) versus 54 mm (3 MW) for the 5SL4363-7. It will physically snap onto the same DIN rail and occupies less space. The wiring is different — the 5SL6102-7CC is 1-pole, so only the line conductor passes through it.

What compliance documentation does Siemens provide for 5SL6102-7CC?

The breaker is rated per EN 60898 (6 kA breaking capacity), overvoltage category III, pollution degree 2, and vibration resistance per IEC 60068-2-6. The housing is halogen-free and silicon-free. Standard Siemens declaration of conformity and CE marking apply.