Siemens 5SL6106-6CC SENTRON MCB, 1P B 6A 6kA 400V

MPN5SL6106-6CC
Active

Siemens SENTRON 5SL6 series, miniature circuit breaker, 1-pole, B characteristic, 6 A rated, 6 kA breaking capacity at 400 V AC, 50/60 Hz, 1 MW width.

$12.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6106-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL6106-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SL6106-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6106-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6106-6CC is a 1-pole SENTRON miniature circuit breaker with a B tripping characteristic, rated 6 A at 400 V AC and a 6 kA breaking capacity per EN 60898. The 6 kA breaking capacity at 400 V AC covers most distribution board fault levels; if your panel's prospective short-circuit current exceeds that, step up to the 10 kA or 15 kA variants in the same 5SL6 family. Rated voltage is 400 V AC for multi-phase operation, 250 V AC single-phase — so it fits both 230/400 V three-phase boards and single-phase sub-distribution. The 50/60 Hz rating covers both mains frequencies without derating. Thermal derating is published: at 40 °C ambient the continuous current drops to 5.66 A, at 50 °C to 5.29 A.

Snap-on DIN rail mount, 1 MW (18 mm) wide, 76 mm deep. Fits any standard 35 mm DIN rail enclosure. Suitable for dry indoor distribution boards. Operating temperature range -40 to 75 °C covers unheated utility rooms and outdoor-adjacent enclosures.

Frequently asked questions

What is the breaking capacity of the 5SL6106-6CC?

6 kA at 400 V AC per EN 60898. That is the standard breaking capacity for this series — suitable for most residential and light commercial distribution boards.

Where can I buy the 5SL6106-6CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

MPN
5SL6106-6CC