Skip to main content
Siemens 5SL6113-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL6113-7 SENTRON MCB, 1P C-Curve 13 A 6 kA

MPN5SL6113-7
Active

Siemens SENTRON 5SL6113-7, 1-pole miniature circuit breaker, C-curve, 13 A rated at 30 °C, 6 kA breaking capacity per EN 60898 and IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6113-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL6113-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL6113-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6113-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6113-7 is a 1-pole SENTRON miniature circuit breaker with a C-trip curve, rated 13 A at 30 °C and breaking 6 kA per EN 60898 and IEC 60947-2. It occupies a single modular width (18 mm) on a DIN rail, installs in any mounting position, and is intended for residential and infrastructure branch-circuit protection.

At 40 °C it derates to 12.37 A; at 45 °C to 11.96 A; at 55 °C to 11.36 A. Plan the load so the branch current stays under the derated value at the expected panel temperature.

Frequently asked questions

What is the breaking capacity of 5SL6113-7?

6 kA per EN 60898 and IEC 60947-2, which is the standard interrupting rating for a residential/infrastructure MCB in this class.

Will 5SL6113-7 drop into a panel specified for 5SL6016-7?

Yes — both are 1-pole SENTRON MCBs on a single modular-width (18 mm) DIN-rail footprint, so the mechanical fit is identical. The difference is the current rating: 5SL6016-7 is a 16 A C-curve, while 5SL6113-7 is 13 A. No rewiring needed if the branch load is within 13 A.

What compliance documentation does Siemens provide for 5SL6113-7?

The breaker carries EN 60898 and IEC 60947-2 ratings (6 kA), is halogen-free and silicon-free, and is rated for overvoltage category III and pollution degree 2. RoHS and REACH declarations are standard from Siemens for this SENTRON series.

Where can I buy 5SL6113-7?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SL6113-7