The Siemens 5SL6113-7CC is a SENTRON 5SL-series miniature circuit breaker — one pole, C-curve trip characteristic, rated 13 A at 400 V AC, with a 6 kA breaking capacity tested to EN 60898. The C-curve (tripping characteristic class C) means it holds 5–10× rated current for short overloads — designed for inductive loads like small motors, fluorescent lighting, and transformer inrush where a B-curve would nuisance-trip. The 72 V DC maximum rating covers control-circuit applications.
Where it goes — deployment context
Sized for residential and infrastructure distribution boards — the 5SL series is a standard DIN-rail MCB line for Siemens SENTRON panels. Energy limiting class 3 means it restricts let-through energy under fault conditions — helps downstream coordination and reduces arc-flash energy at the panel. Ambient temperature range -40 to 75 °C, with periodic exposure to +55 °C at 95% humidity — suitable for outdoor enclosures or unconditioned electrical rooms.