Skip to main content
Siemens 5SL6116-6MB — 1-Pole MCB (DIN Rail)

Siemens 5SL6116-6MB SENTRON MCB, 1P B 16A 6kA

MPN5SL6116-6MB
Active

Siemens SENTRON miniature circuit breaker, 5SL6116-6MB, 1-pole, B-characteristic, 16 A, 6 kA breaking capacity per EN 60898, 230/400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6116-6MB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SL6116-6MB — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation classNo
Overvoltage categoryIII
5SL6116-6MB — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6116-6MB — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL6116-6MB is a 1-pole miniature circuit breaker with a B tripping characteristic, rated 16 A at 30 °C and 400 V AC supply voltage.

The B-curve trips between 3 and 5 times rated current — 48 to 80 A for this 16 A unit — making it a fit for resistive and general-purpose loads where inrush isn't severe. The 6 kA breaking capacity at 230/400 V AC is enough for most residential and light commercial distribution boards; if your fault level at the panel is higher, you'd step up to the 10 kA variant in the same 5SL6 family.

The -40 °C to 75 °C operating range covers unheated utility rooms and outdoor-adjacent enclosures. Touch protection on the terminals is built in; no finger-safe covers needed.

Frequently asked questions

Where can I buy 5SL6116-6MB and how do I get a price?

The 5SL6116-6MB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

When sourcing 5SL6116-6MB, what's the closest functional second-source — 5SL3116-6MB?

The 5SL3116-6MB is the closest peer: same 1-pole B-curve 16 A rating, same 18 mm footprint, but with a 4.5 kA breaking capacity instead of the 5SL6116-6MB's 6 kA. It drops into the same panel position without rewiring, but verify the fault level at the board — if you need 6 kA, the 5SL6116-6MB is the correct call.

Will 5SL6116-6MB drop into a panel that was specified around 5SL3116-6MB without rewiring?

Yes — both share the same 18 mm width, 76 mm depth, and DIN-rail mounting. The 5SL6116-6MB is a direct mechanical swap for the 5SL3116-6MB. No rewiring or busbar adjustment needed; just confirm the higher 6 kA breaking capacity is compatible with your installation's prospective fault current.

What compliance documentation does this brand provide for 5SL6116-6MB?

The 5SL6116-6MB is rated per EN 60898 for breaking capacity, carries overvoltage category III and pollution degree 2 ratings, and is designed for residential/infrastructure suitability. The SENTRON series typically provides CE, RoHS, and REACH declarations — consult the product documentation for specific certificates.

MPN
5SL6116-6MB