Siemens 5SL6163-7CC — SENTRON 1-pole MCB, C-curve, 63 A
The C-curve trips between 5× and 10× rated current, so a 63 A breaker clears a short-circuit fault at 315–630 A peak. On a 63 A resistive load at 40 °C the continuous rating drops to 58.09 A; at 50 °C it is 52.73 A — factor the derating if the panel runs warm. Single-pole switching, rated 250 V AC single-phase or up to 440 V AC multi-phase.
Halogen-free and silicon-free construction, sealable (can be padlocked in OFF position). Touch protection integrated on the busbar side.