The 5SL6202-7CC: The C-curve trips magnetically between 5 and 10 times rated current (10–20 A for this 2 A unit), which suits loads like lighting banks, control transformers, and small motors that draw a brief inrush. The 6 kA breaking capacity per EN 60898 means it can safely interrupt a fault current up to 6,000 A at 400 V AC — standard for most residential and light commercial sub-distribution boards. The 2-pole design switches both phase and neutral, and the 2 MW width (36 mm) fits a standard DIN-rail enclosure with room for adjacent breakers. Power loss is 1.3 W per pole in hot operating state — negligible for panel thermal budgeting.
Panel integration
Depth is 76 mm, height 90 mm, width 36 mm (2 MW). Sealable to prevent unauthorized operation. Halogen-free and silicon-free construction.