Skip to main content
Siemens 5SL6205-7RC — 2-Pole MCB (DIN Rail)

Siemens 5SL6205-7RC SENTRON MCB, 0.5 A, 2-Pole, C Curve, 7.5

MPN5SL6205-7RC
Active

Siemens SENTRON miniature circuit breaker, 5SL6205-7RC, 0.5 A rated current, 2-pole, C tripping characteristic, 7.5 kA breaking capacity per EN 60898, 2 modular width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SL6205-7RC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure

Electrical

5SL6205-7RC — Electrical
ParameterValue
Number of poles2

Protection

5SL6205-7RC — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII

Mechanical

5SL6205-7RC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors

Environmental

5SL6205-7RC — Environmental
ParameterValue
Pollution degree2

Specifications

5SL6205-7RC — Specifications
ParameterValue
Energy Limitation ClassNo

Product details

The Siemens SENTRON 5SL6205-7RC is a 0.5 A, 2-pole miniature circuit breaker with a C tripping characteristic and a 7.5 kA breaking capacity per EN 60898. It occupies 2 modular width units (36 mm) on a DIN rail, making it a standard panel component for protecting lighting, control transformers, and small resistive loads in residential or infrastructure panels.

Ratings and what they mean for the panel

Rated 0.5 A at both AC and at 30 °C ambient, this breaker is sized for very low-current branch circuits — think pilot lights, signal transformers, or control power feeds where a standard 1 A or higher breaker would not provide adequate overcurrent protection. The C curve (magnetic trip between 5× and 10× In) means it tolerates moderate inrush without nuisance tripping, suitable for small inductive loads like contactor coils or relay banks. Breaking capacity of 7.5 kA per EN 60898 covers most residential and light commercial fault levels. For higher available fault currents (e.g., industrial mains), verify the upstream SCCR coordination — this breaker is not rated for industrial distribution panels without a current-limiting upstream device. Voltage ratings: 250 V AC single-phase, 415 V AC three-phase, with a maximum of 440 V AC in multi-phase operation. DC rating is 72 V maximum, so it can also serve DC control circuits within that limit.

Physical fit and installation

Dimensions: 36 mm wide (2 MW), 76 mm deep, 90 mm tall. Mounts on standard DIN rail in any position. Installation depth of 70 mm leaves clearance for wiring behind the rail.

Frequently asked questions

Will 5SL6205-7RC drop into a panel specified around 5SL6132-6MB without rewiring?

No — the 5SL6205-7RC is 2 modular width units (36 mm) versus the 5SL6132-6MB's 1 unit (18 mm). Both share the same 76 mm depth and 90 mm height, so the panel depth and height fit, but the 2-pole breaker occupies double the DIN-rail space. Wiring also differs: the 5SL6205-7RC switches both poles; the 5SL6132-6MB is single-pole. A direct swap without rewiring is not possible.

MPN
5SL6205-7RC