At 30 °C the 6 A rating holds; derate to 5.66 A at 40 °C, 5.48 A at 45 °C, 5.29 A at 50 °C, and 5.1 A at 55 °C — account for the ambient temperature inside the enclosure when sizing for continuous load.
Overall dimensions are 90 mm height, 36 mm width, 76 mm depth. Sealable, halogen-free, and silicon-free construction.
Lifecycle status is active-current production. This is not a phase-out or NRND line.